13. Approvals and conformities

No product norm exists for Thyristor switches so that a useful norm
structure can be built up based on the corresponding basic norms
ensuring reliable application and comparison potential.
CAUTION
Thyristor switches are not devices for disconnection in the
sense of EN 50110-1 and may therefore be operated only
in connection with a suitable mains isolating device (e.g.
switch, isolating link).
Approvals and conformities for Thyro-S are available
• Quality standard according to EN ISO 9001
• UL registration, file no. E 135074, with consideration to Canadian
National Standard C 22.2 No. 14-95
• Brand circuit protection must be provided and sized according
National Electrical Code and any additional local codes
• CE conformity
• Low voltage directive 2006/95/EG
• EMV directive 2004/108/EG
• RoHS
90
In Detail
Conditions for usen
Built-in unit (VDE 0160)
General requirements
Design, vertical installation
Operating conditions
Operating location, industry sector
Temperature behaviour
Storage temperature
Transport temperature
Operating temperature
Load class
1
Humidity class
F
Overvoltage category
ÜIII
Degree of pollution
2
Air pressure
Safe isolation up to 500 V mains voltage:
Air and creeping distances
Test voltage
Tests according to
EMV noise emission
Noise suppr. control device Class A
EMV noise resistance
Compatibility level
Class 3
ESD
8 kV (A)
Electromagnetic fields
10 V/m
Burst
mains lines
2 kV (A)
control lines
2 kV (A)
Surge mains lines
2 kV unsym.
1 kV sym.
control lines
0.5 kV
Line-conducted
91
EN 50 178
EN 60146-1
EN 60 146-1-1; K. 2.5
CISPR 6
EN 60 146-1-1; K 2.2
-25°C
- +55°C
-25°C
- +70°C
-10°C
- +40°C
with external cooling (280A)
-10 °C - +45 °C with self air cooling
-10°C - +55°C
with reduced type current -2%/°C
EN 60 146-1-1 T.2
EN 50 178 Tab. 7
EN 50 178 Tab. 3
EN 50 178 Tab. 2
EN
900 mbar * 1000 m above NN
EN 50 178 Chap. 3
casing / mains potential > 5.5 mm
casing / control potential > 2.5 mm
mains voltage /contr. potent. ≥ 10 mm
interface /contr. Potent. -/-
mains voltages interact 2.5 mm
EN 50 178 Tab 18
EN 60 146-1-1 4.
EN 61000-6-4
EN 55011, CISPR 11
EN 61000-6-2
EN 61000-2-4
EN 61000-4
EN 61000-4
EN 61000-4-5
EN 61000-4
EN 61000-4
EN 61000-4-6