Fig. 6 Operation Thyro 1S...H RL1
H 100
LED
GREEN ON
LED
GREEN
Diagnosis
H 230
H 250
LED
RED
LOAD FAULT
S1-4
Without function
S1-3
Thyro-Tool Mode
S1-2
Operating mode
S1-1
Operating mode
R205
Load monitoring LOAD FAULT
74
chapter 3.1
chapter 3.1
chapter 2.3
5. Interfaces
The Thyristor Switch of type range Thyro-S...1 are all equipped with
a system interface at terminal strip X22. Either a bus module or a PC
interface with a PC connection can be operated from this.
5.1 Bus module at the system interface
The optional bus module enables the Thyro-S range Power Controller
to be connected to a field bus. The bus module is hereby connected
to the Power Controller's system interface (terminal strip X22) with
prefabricated cables on the bus module side. Up to eight Thyro-S (or
also combined with Thyro-A) can be connected to the bus system
with one bus module, e.g. Profibus-DP, Modbus RTU, CANopen or
DeviceNet.
The bus module connection configuration is identical for all available
bus modules. Further information can be obtained from the operating
instructions of the respective bus module.
REMARK
Further useful functions for the application are possible
via field bus by the access of set point value, actual va-
lues, parameters as well as fault diagnosis.
5.2 PC-Interface RS232 at the system interface
The Power Controller is connected to a PC via the serial interface
(COM1, COM2 ...) with the PC-INTERFACE RS232. In addition, an
RS232-DATALINE, Order No. 0048764 is needed (not crossed, the
connection 2, 3, 4, 5 and 7 are used).
The PC-INTERFACE RS232 must be connected to the terminal strip
X22 according to the instructions included.
75