Table 5-3: Communication Mapping Table - Eaton MVX9000 User Manual

Af drives, cutler-hammer
Hide thumbs Also See for MVX9000:
Table of Contents

Advertisement

Group 90 — Communications
90.06 to 90.23
Communication Only
These parameters are used when controlling and monitoring
Parameters
the MVX with a PC. See Table 5-3.

Table 5-3: Communication Mapping Table

Modbus Groups
Description
0705H
90.06
Communication frequency
reference
0706H
90.07
Communication command
0707H
90.08
Communication for EF/
RESET
0708H
90.09
Status monitor for error
code
MVX9000 User Manual
Range
0.0 to 400.0 Hz (Default: 0.0)
Bit 0-1: 00 no function
01 Stop
10 Run
11 JOG + Run
Bit 2-3: Reserved
Bit 4-5: 00 no function
01 Forward
10 Reverse
11 Change direction
Bit 6-15: Reserved
Bit 0: 1 EF On
Bit 1: 1 Reset
Bit 2-15: Reserved
00: No Fault occurred
01: Over-current (oc)
02: Over-voltage (ov)
03: Overheat (oH)
04: Overload (oL)
05: Overload 1 (oL1)
06: Overload 2 (oL2)
07: External Fault (EF)
08: CPU Failure 1 (CF1)
09: CPU Failure 2 (CF2)
10: CPU Failure 3 (CF3)
11: Hardware Protection Failure (hpF)
12: Over-current During Accel (OCA)
13: Over-current During Decel (OCd)
14: Over-current During Steady State
(OCn)
15: Ground Fault or Fuse Failure
(GFF)
16: Reserved
17: 3-Phase Input Power Loss
18: External Pause Function (bb)
19: Auto Adjust Accel/Decel Failure
(cFA)
20: Software Protection Code (codE)
5-65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents