Trial Operation And Testing - Daikin FDMQ09RVJU Installation Manual

R410a split series
Hide thumbs Also See for FDMQ09RVJU:
Table of Contents

Advertisement

(b) Select external static pressure with the remote controller.
Check with Mode No. [21] per indoor unit that the SECOND
CODE No. for the above "Air volume adjustment" is set to "01"
(OFF). (The SECOND CODE No. is factory set to "01" (OFF).)
Change the SECOND CODE No. by referring to the table
below according to the external static pressure of the duct to
be connected.
Table 5 09/12 class
External static
Mode No.
pressure
30Pa
40Pa
50Pa
60Pa
70Pa
80Pa
13(23)
90Pa
100Pa
110Pa
120Pa
130Pa
140Pa
150Pa
Table 5 15/18/24 class
External static
Mode No.
pressure
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
13(23)
110Pa
120Pa
130Pa
140Pa
150Pa
10-2 SETTING WHEN AN OPTIONAL ACCESSORY IS
ATTACHED
• For setting when attaching an optional accessory, refer to the
installation manual attached to the optional accessory.
10-3 SETTING FILTER SIGN
• A message to inform the air filter cleaning time will be
indicated on the remote controller.
• Set the SECOND CODE No. shown in the Table 6 according
to the amount of dust or pollution in the room.
• The periodical filter cleaning time can be shortened
depending on the environment.
Table 6
Hours until
Contamination
indication
Approx.
Normal
2500 hrs
More
Approx.
contaminated
1250 hrs
With indication
No indication*
* Use "No indication" setting when cleaning indication is not
necessary such as the case of periodical clean ing being carried out.
10-4 REMOTE CONTROL SETTINGS
<In the case of using a wireless remote controller>
• In the case of using a wireless remote controller, address
settings for the wireless remote controller are required.
For settings, refer to the installation manual provided with the
wireless receiver kit.
15
FIRST
SECOND
CODE No.
CODE No.
03
04
05
06
07
08
6
09
10
11
12
13
14
15
FIRST
SECOND
CODE No.
CODE No.
05
06
07
08
09
6
10
11
12
13
14
15
FIRST
SECOND
Mode No.
CODE No.
CODE No.
01
0
02
10(20)
01
3
02

11. TRIAL OPERATION AND TESTING

11-1 TRIAL OPERATION AND TESTING
• Trial operation should be carried out in either COOL or HEAT
operation.
Measure the supply voltage and make sure that it
1.
is within the specified range.
In COOL operation, select the lowest
2.
programmable temperature;
in HEAT operation, select the highest
programmable temperature.
Carry out the trial operation following the
3.
instructions in the operation manual to ensure
that all functions and parts, are working properly.
• To protect the air conditioner, restart operation is disabled
for 3 minutes after the system has been turned off.
After trial operation is complete, set the
4.
temperature to a normal level (78°F to 82°F (26°C
to 28°C) in COOL operation, 68°F to 75°F (20°C to
24°C) in HEAT operation).
• When operating the air conditioner in COOL operation
in winter, or HEAT operation in summer, set it to the trial
operation mode using the following method.
Refer to For wired remote controller on page 16.
Refer to For wireless remote controller on page 17.