Setting Charge/ Discharge Profile + Backup Power - SolarEdge SE7600A-US Installation Manual

Storedge solution with backup
Hide thumbs Also See for SE7600A-US:
Table of Contents

Advertisement

 a.  Select Energy Manager è Storage Control. The following is displayed:
B a c k u p
A C
 b.  Select Backup Rsvd and set the required level of reserved energy as percentage of the battery 
capacity:
 
For backup power + Smart Energy Management - according to user requirement
o
 
For backup-only - according to battery manufacturer recommendation, if provided.
o
If you set the Backuo Rsved to a value other than 0%, the following is displayed:
B a c k u p
G r i d
A C
 c.  Select Grid Charge and one of the following options:
 
Enable: Charge from both PV and grid to reach backup reserved value
l
 
Disable: Charge from PV only to reach backup reserved value
l

Setting Charge/ Discharge Profile + Backup Power

In this mode, you first set the system to charge/ discharge profile   ( for time-of-use arbitrage) and the level 
of charging the battery from AC. Then, you set up the level of stored energy to be reserved for backup.
To set up Charge/ Discharge Profile (TOU) + Backup Power:
 1.  Access the Energy Ctrl. menu as described above.
 2.  Select Time of Use.The Energy Manager screen changes to display the following:
L i m i t
E n e r g y
S e t
S t o r a g e
 3.  From the Energy Manager menu select Set Calendar. The following screen is displayed, showing 
options for calendar setting:
S e r v e r
L o a d
 4.  Do one of the following:
 
To load a time-of-use table from the monitoring platform, refer to 
l
https://www.solaredge.us/sites/default/files/storedge_charge_discharge_
profile_programming.pdf .
 
To load a time-of-use table from the SolarEdge SD card (contact SolarEdge to 
l
obtain it), insert the card to the slot labeled "Card" on the communication board 
and select Load SD. From the displayed list select the directory and the table 
(filename).
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
R s v d
< N / A >
C h a r g e
L i < N o n e >
R s v d
< 2 0 % >
C h a r g e
< E n >
C h a r g e
L i < N o n e >
C o n t r o l < D i s >
C t r l
< T O U >
C a l e n d a r
C o n t r o l
S y n c
< D i s >
S D
< N / A >
Chapter 10: System Configuration
89

Advertisement

Table of Contents
loading

This manual is also suitable for:

Seauto-tx-5000

Table of Contents