04 Communication Parameters
When co ntrolling by com mun catio n,
it needs to conn ect th e driv e an d PC by
IFD6530 or IFD650 0 co nverter.
Communication Address
Settings
If the AFE unitis controlled by RS-485 serial communication, the communication address for this AFE unit
must be set via this parameter. And the communication address for each AC motor drive must be different
and unique.
Transmission Speed
Settings
This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.) and
AFE2000 unit.
Transmission Fault Treatment
Settings
This parameter is set to how to react if transmission errors occur.
Time-out Detection
Settings
It is used to set the transmission time between communication and keypad.
Communication Protocol
Settings
Chapter 11 Description of Parameter SettingsAFE2000 Series
1~254
4.8~115.2kbits/s
0: Warn and continue operation
1: Warn and ramp to stop
2: Reserved
3: No treatment and no warn
0.0~100.0sec
0.0: No detection
0:7,N,1 for ASCII
1:7,N,2 for ASCII
2:7,E,1 for ASCII
3:7,O,1 for ASCII
4:7,E,2 for ASCII
11-85
This parameter can be set during the operation.
Serial
co mmun icati on
1
6
1:+EV
2:GND
3:SG-
4:SG+
RS-485
5:NC
6:NC
Factory Setting: 1
Factory Setting: 19.2
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 13