Delta Electronics AFE075A43A User Manual page 20

Afe2000 series. active front end unit
Table of Contents

Advertisement

Chapter 5 Control TerminalsAFE2000 Series
SINK(NPN)/SOURCE(PNP)Mode Switching Terminals.
1
Sink Mo de
with i nternal power (E 2 4Vdc)
3
Sink Mo de
with e xternal power
external power +24V
Terminals
Digital control signal common
E24V
(Source)
COM
Digital control signal common (Sink)
MI1
~
Multi-function input 1~8
MI8
Digital frequency signal common
DCM
Multi-function Output 1
MO1
(photocoupler)
Multi-function Output 2
MO2
(photocoupler)
Multi-function Output Common
MCM
(photocoupler)
S1
The factory setting is short circuit.
Power removal safety function for EN954-1 and IEC/EN61508
DCM
MI1
MI2
MI8
E24V
COM
inte rn al circui t
DCM
MI1
MI2
MI8
+24V
COM
DCM
inte rn al circui t
Terminal Function
2
Source Mo de
with i nternal power (E24Vd c)
4
Source Mo de
with e xternal power
external power +24V
Factory Setting (NPN mode)
+24V±5% 200mA
Factory setting is short circuit status.
The parameters used to set multi-function inputs MI1~MI8
are Pr.02-01~Pr.02-08.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11V
Common for multi-function input terminals.
The AFE2000 releases various monitor signals, such as
drive in operation, frequency attained and overload
indication, via transistor (open collector).
Max 48Vdc 50mA
5-18
MI1
MI2
MI8
DCM
COM
inte rn al c ircui t
E24V
MI1
MI2
MI8
+24V
COM
DCM
inte rn al c ircui t
dc
MO1
MO2
MCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents