02 Digital Input/Output Parameters
Multi-Function Input Command 1 (MI1)
Multi-Function Input Command 2 (MI2)
Multi-Function Input Command 3 (MI3)
Multi-Function Input Command 4 (MI4)
Multi-Function Input Command 5 (MI5)
Multi-Function Input Command 6 (MI6)
Multi-Function Input Command 7 (MI7)
Multi-Function Input Command 8 (MI8)
Settings 0: Disable
 This parameter is user defined setting to select the functions for each multi-function terminal.
Summary of function settings:
Settings
0
No function
1
RUN
2
STOP
3
EF1
4
RESET
5
Master/Slave
6
Enable
7
EF2
8
EF3
9
oH3
Chapter 11 Description of Parameter SettingsAFE2000 Series
1: RUN
2: STOP
3: EF1
4: RESET
5: master/slave
(will be available soon)
6: enable
7: EF2
8: EF3
9: oH3
Functions
Output terminal has no function
This terminal is a latched contact.
The terminal setting is valid when Pr.01-04=1 (control by
external terminal).
This terminal is a latched contact
The terminal setting is valid when Pr.01-04=1 (control by
external terminal).
Emergency stop 1
When the fault is cleared, this terminal allows AFE2000 to
perform the reset.
(not supported)
If this terminal is set, AFE2000 is enabled when the
contact is triggered.
Emergency stop 2
Emergency stop 3
Reactor overheat warning
When this terminal is triggered on, it will signal a reactor
overheat warning.
 This parameter can be set during the operation.
Descriptions
-
11-79
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4
Factory Setting: 5
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0