Chapter 4 Main Circuit TerminalsAFE2000 Series
Main Circuit Terminals
Frame B
+
DC-
DC+
R/L1
S/L2
T/L3
r1/l1
s1/l2
t1/l3
DETECTION
POWER
Main circuit terminals:
R(L1), S(L2), T(L3),
Max. Wire
Models
AFE075A23A
AFE075A43A
(21.2mm
AFE150A43A
UL installations must use 600V, 75℃ or 90℃ wire. Use copper wire
only.
DC+ & DC-: must use 1kV Wire.
NOTE
Terminal r1/l1, s1/l2,
Wire Gauge:20AWG [0.5mm²] ~ 14 AWG [2.1mm²]
t1/l3:
Torque: 12 kg-cm [10.4 lb-in.] (1.18Nm) (±10%)
If additional terminal is needed when wiring, please refer to Figure 1 for
additional terminal dimension.
After crimping the wire to the ring lug please apply the UL approved R/C
(YDPU2) heat shrink tubing rate min 600Vac to the terminal. The insulation shall
be all over the live part. Please refer to Figure 2.
Detection wire
Figure 1
Power wire
Figure 1
4-14
, DC+, DC-
Min. Wire Gauge
Gauge
6 AWG (13.3mm
4 AWG
8 AWG (8.4mm
2
)
6 AWG (13.3mm
Torque
(±10%)
2
)
M5
2
)
35kg-cm
(30.4 lb-in.)
2
)
(3.434Nm)
Figure 2
Figure 2