Parts List; Required Tools; Site Requirements - Allen-Bradley ArmorStratix 5700 Installation Instructions Manual

Ethernet managed switches
Hide thumbs Also See for ArmorStratix 5700:
Table of Contents

Advertisement

ArmorStratix 5700 Ethernet Managed Switches

Parts List

Verify that you have these items.
1
2
1
ArmorStratix™ 5700 switch
2
Documentation
At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

Required Tools

Obtain these tools:
• An IP67-rated cordset or patchcord with a female-end, 4-pin mini connector to provide 24V DC power to the switch
• Ratcheting torque screwdriver that exerts up to 1.69 N
• #6 ring terminal lug for 5.3 mm
• Crimping tool, such as Thomas & Bett part number WT2000, ERG-2001, or equivalent
2
• 5.3 mm
(10 AWG) copper ground wire, such as Belden part number 9912 or equivalent
• Wire-stripping tool
• For panel-mounting without a DIN rail, M5 or #10-24 or #10-32 bolts or screws with 1.27 cm (0.5 in.) O.D. flat washers
For simplified cabling, the automatic medium-dependent interface crossover (auto-MDIX) feature is enabled by default on the switch. With
auto-MDIX enabled, the switch detects the required cable type for copper Ethernet connections and configures the interfaces accordingly. You can
use either a crossover or a straight-through cable for connections to a 10/100 or 10/100/1000 Ethernet switch port, regardless of the type of device
on the other end of the connection.

Site Requirements

Observe these site requirements:
• Clearance to front and rear panels meets these conditions:
– Front-panel status indicators can be easily read.
– Access to ports is sufficient for unrestricted cabling.
– Front-panel DC power connectors and the alarm relay connector are within reach of the connection to the DC power source.
• To prevent the switch from overheating, observe the following minimum clearances:
– Top and bottom: 50.8 mm (2.0 in.)
– Sides: 50.8 mm (2.0 in.)
– Front: 50.8 mm (2.0 in.)
• Temperature surrounding the unit does not exceed 60 °C (140 °F).
• For 10/100 ports and 10/100/1000 ports, the cable length from a switch to an attached device cannot exceed 100 m (328 ft).
• For maximum noise immunity, X-code shielded cables must be used on M12 uplink ports. For recommended M12 media, refer to
http://ab.rockwellautomation.com/Connection-Devices/EtherNet-Media.
• Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent lighting fixtures.
• Connect the unit to only an IP67-rated power supply. Rockwell Automation offers a Bulletin 1607 IP67-rated power supply to provide
24V DC power to the switch.
4
m (15 in
(10 AWG) wire, such as Thomas & Bett part number 10RC6 or equivalent
Rockwell Automation Publication 1783-IN017A-EN-P - July 2017