Confirm Installation; Specifications - Allen-Bradley ArmorStratix 5700 Installation Instructions Manual

Ethernet managed switches
Hide thumbs Also See for ArmorStratix 5700:
Table of Contents

Advertisement

ArmorStratix 5700 Ethernet Managed Switches

Confirm Installation

To confirm the installation, power on the switch, and verify that the switch powers up.
The time that is required for the switch to start up is directly related to your switch configuration. Start time is negatively affected by such things as
the following:
• Spanning Tree Learning mode
• Number of files or images in onboard memory
To test the switch, follow these steps.
1. Power on the switch.
If the switch that is directly connected to a DC power source, locate the circuit breaker on the panel board that services the DC circuit, and
move the circuit breaker to the On position.
2. Verify the start-up sequence.
The Setup status indicator blinks green as the IOS software image loads. If the routine fails, the Setup status indicator turns red.
IMPORTANT
Start-up failures are usually fatal to the switch. Contact your Rockwell Automation representative immediately if your switch does not complete
the start sequence successfully.

Specifications

Attribute
Temperature, operating
Temperature, ambient
Enclosure type rating
Switch power input rating
Alarm relay rating
Isolation voltage
Wire size, ground connection
Wire size, power connector for IP67 cable
Wire size, Alarm connector for IP67 cable
Torque, ground lug screw
Torque, power ports
Torque, alarm, console, Ethernet ports
(M12 connectors)
Torque, power supply connector
(mini-change)
Torque, SD card door captive screws
Pilot duty rating
Operating and storage altitude
Dimensions (H x W x D), approx
Weight
10
1783-ZMS8TA
1783-ZMS16TA
-40...+60 °C (-40...+140 °F
60 °C (140 °F)
IP66 rated for protection against dust and water jets
IP67 rated for protection against dust and submersion in water
NEMA Type 4
ATTENTION: The switch is IP66/IP67- and NEMA Type 4-compliant only when all IP66/IP67 cables are mated and torqued appropriately or with the supplied
dust caps attached.
12...48V DC, 1.5 A
12...48V DC, 1.8 A
60 V (continuous), basic insulation type, DC power ports to ground, and PoE power ports to ground
No isolation between individual Ethernet ports
No isolation between PoE Power and Ethernet ports
No isolation between Console port and system
2
4.0 mm
(12 AWG) min, stranded copper wire
600V 16 AWG, 105 °C (221 °F)
0.4 N•m (3.5 in•lb)
0.23 N•m (2.0 in•lb)
0.5...0.8 N•m (4.43...7.08 in•lb) for mating cables or dust caps
1.13 N•m (10 in•lb)
1.8...2.2 N•m (15.93...19.47 in•lb)
Alarm not rated
Up to 4570 m (15,000 ft)
243.8 x 237.49 x 86.3 mm
243.8 x 300.99 x 68.07 mm
9.6 x 9.35 x 3.4 in.
9.6 x 11.85 x 2.68 in.
3.26 kg (7.19 lb)
3.30 kg (7.28 lb)
Rockwell Automation Publication 1783-IN017A-EN-P - July 2017
1783-ZMS4T4E2TGP,
1783-ZMS24TA
1783-ZMS4T4E2TGN
PoE/PoE +: 48...54V DC, 2.9 A
12...48V DC, 2.0 A
Non-PoE: 9.6...60V DC, 2.9 A
30V DC, 1.0 A or 48V DC, 0.5 A
300V, 22 AWG,105 °C (221 °F)
243.8 x 374.65 x 68.07 mm
243.8 x 237.49 x 86.3 mm
9.6 x 14.75 x 2.68 in.
9.6 x 9.35 x 3.4 in.
4.02 kg (8.86 lb)
3.26 kg (7.19 lb)
1783-ZMS8T8E2TGP,
1783-ZMS8T8E2TGN
PoE/PoE+: 48...54V DC, 3.3 A
Non-PoE: 9.6...60V DC, 3.3 A
243.8 x 300.99 x 68.07 mm
9.6 x 11.85 x 2.68 in.
3.30 kg (7.28 lb)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents