Requirements Table - ABB ACS580-01 Hardware Manual

0.75 to 250 kw, 1.0 to 350 hp
Table of Contents

Advertisement

68 Planning the electrical installation

Requirements table

The following table shows how to select the motor insulation system and when an
optional drive du/dt and common mode filters and insulated N-end (non-drive end)
motor bearings are required. Ignoring the requirements or improper installation may
shorten motor life or damage the motor bearings and voids the warranty.
Motor
Nominal AC supply
type
voltage
ABB motors
Random-
U
< 500 V
N
wound
M2_,M3_
and M4_
Form-
380 V < U
wound
HX_ and
AM_
Old*
380 V < U
form-
wound
HX_ and
modular
Random-
0 V < U
N
wound
HX_ and
AM_ **
*
manufactured before 1.1.1998
**
For motors manufactured before 1.1.1998, check for additional instructions with the
motor manufacturer.
Motor
insulation
system
Standard
< 690 V
Standard
N
< 690 V
Check with
N
the motor
manufacturer.
< 500 V
Enameled
wire with fiber
glass taping
Requirement for
ABB du/dt and common mode filters,
insulated N-end motor bearings
P
< 100 kW
100 kW < P
N
and frame size
< IEC 315
IEC 315 < frame size <
P
< 134 hp
134 hp < P
N
and frame size
< NEMA 500
-
+ N
n.a.
+ N + CMF
+ du/dt with voltages over 500 V + N +
CMF
+ N + CMF
< 350 kW
N
or
IEC 400
< 469 hp
N
or
NEMA 500 < frame
size < NEMA 580

Advertisement

Table of Contents
loading

Table of Contents