14.3 Analog Inputs

14.3.1 Primary Input (Terminals 5 and 6 of M1)

The REVO M thyristor unit has 1 analog inputs for the analog setpoint.
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 4÷20mA) proceed as follows:

14.3.2 Primary Input calibration procedure

When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
Give the power supply.
With Control Panel go in the Hardware menu ( = 5)
Set the input signal to the min value (ex. 0V for 0÷10V or 4mA for 4÷20mA)
Select the parameter  then press F ( Flashing)
Press Up key ( on display)
Press F key to confirm ( on display)
Set the input signal to the max value (ex.10V for 0÷10V or 20mA for 4÷20mA)
Select the parameter  then press F ( Flashing)
Press Up key ( on display)
Press F key to confirm ( on display)
- The Input calibration procedure is done.
CD-Eng-REVO-M-1PH-60-210A-Thyristors-Units
Type
Input features
010V (default)
Impedance
POT
Impedance
420mA
Impedance
33
15K
10K min
100