Remaining Connection Status; Parallel Redundancy Protocol (Prp) - GE M60 Instruction Manual

Motor protection system
Hide thumbs Also See for M60:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
— This represents the receiver status of each channel. If the value is "OK," teleprotection is enabled and
CHANNEL 1 STATUS
data is being received from the remote terminal; If the value is "FAIL," teleprotection enabled and data is not being received
from the remote terminal. If "n/a," teleprotection is disabled.
— Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle.
CHANNEL 1 LOST PACKETS
The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS  CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION
check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the "FAIL" message
displays. The "N/A" value appears if the local relay ID is set to a default value of "0," the channel is failed, or if the
teleprotection inputs/outputs are not enabled.

6.3.20 Remaining connection status

ACTUAL VALUES  STATUS  COMM STATUS REMAINING CONNECT
 COMM STATUS
 REMAINING CONNECT
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
— The number of IEC 61850 connections remaining.
MMS TCP

6.3.21 Parallel Redundancy Protocol (PRP)

The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES  STATUS  PRP STATUS
 PRP STATUS
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
menu.
— This value displays the current state of the communications channel identification
MMS TCP(max 5)
5
MODBUS TCP (max 4)
4
DNP TCP(max 2)
2
IEC-104 TCP(max 2)
2
SFTP (max 4)
4
Total Rx Port A:
0
Total Rx Port B:
0
Mismatches Port A:
0
Mismatches Port B:
0
Total Errors:
0
Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 0 to 4
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
STATUS