STATUS

6.3 Status

6.3.1 Motor

ACTUAL VALUES  STATUS  MOTOR
 MOTOR
The
MOTOR STATUS
The
MOTOR THERMAL CAPACITY USED
value.
The
ESTIMATED TRIP TIME ON OVERLOAD
6
assuming that the motor current remains at its current level. It is obtained from the thermal model curve and takes into
account that some percent of the thermal capacity has already been used.
The
THERMAL LOCKOUT TIME
value to the level when thermal start inhibit is removed and new motor start is permitted. The
value displays only when the motor is offline. For details of lockout time calculations, see the Thermal Model section of
Chapter 5.
The
START/HOUR LOCKOUT TIME
from the Maximum Starting Rate, Time Between Starts, and Restart Delay elements, respectively.
The
TOTAL MOTOR LOCKOUT TIME

6.3.2 Contact inputs

ACTUAL VALUES  STATUS  CONTACT INPUTS
 CONTACT INPUTS
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, 'Cont Ip 1' refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
6-4
MOTOR STATUS:
Offline
MOTOR THERMAL
CAPACITY USED: 0%
ESTIMATED TRIP TIME
ON OVERLOAD: Never
THERMAL LOCKOUT
TIME: 0 min
START/HOUR LOCKOUT
TIME: 0 min
TIME-BTWN-STARTS LO
TIME: 0 min
RESTART DELAY LO
TIME: 0 s
TOTAL MOTOR LOCKOUT
TIME: 0 min
value reflects operating state of the motor.
represents the thermal model accumulated thermal capacity used as a percentage
value represents the estimated time to trip (in seconds) from the thermal model
reflects the calculated time required for the thermal capacity used to decay from its current
,
TIME-BTWN-STARTS LO TIME
value is calculated as the maximum of all lockout times shown in this menu.
Cont Ip 1
Off
Cont Ip xx
Off
, and
RESTART DELAY LO TIME
Range: On, Off
Range: On, Off
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
THERMAL LOCKOUT TIME
lockout time values are calculated