The thermal model is the primary protective function of the relay. It consists of the following five key functions:
Thermal model curve (overload)
Overload pickup level
Unbalance biasing of the motor current while the motor is running
Motor cooling time constants
Biasing of the thermal model based on hot/cold information and/or measured stator temperature
The algorithm integrates both stator and rotor heating into a single model. The motor heating level is maintained in the
thermal capacity used register. When the motor has been stopped for a long time, it is at ambient temperature and
thermal capacity used is zero. When the motor is in overload, the output operand is set once the thermal capacity used
reaches 100%.
5-194
HOT/COLD SAFE
STALL RATIO: 1.00
RTD BIAS:
Disabled
RTD BIAS MINIMUM
40 C
RTD BIAS CENTER
POINT: 130 C
RTD BIAS MAXIMUM:
155 C
START INHIBIT
TCU MARGIN: 0%
VOLTAGE DEPENDENT
FUNCTION: Disabled
VOLTAGE DEPENDENT
MIN MOTOR VOLTS: 80%
VD VOLTAGE LOSS:
Off
VD STALL CURRENT @
MIN V: 4.50 x FLA
VD SAFE STALL TIME @
MIN V: 20.0 sec.
VD ACCELL. INTERSECT
@ MIN V: 4.00 x FLA
VD STALL CURRENT @
100% V: 6.00 x FLA
VD SAFE STALL TIME @
100% V: 10.0 sec.
VD ACCELL. INTERSECT
@100% V: 5.00 x FLA
THERMAL MODEL
BLOCK: Off
THERMAL MODEL
TARGETS: Self-Reset
THERMAL MODEL
EVENTS: Disabled
Range: 0.01 to 1.00 in steps of 0.01
Range: Disabled, Enabled
Range: 0 to 250°C in steps of 1
Range: 0 to 250°C in steps of 1
Range: 0 to 250°C in steps of 1
Range: 0 to 25% in steps of 1
Range: Disabled, Enabled
Range: 60 to 99% in steps of 1
Range: FlexLogic operand
Range: 1.50 to 20.00 x FLA in steps of 0.01
Range: 0.1 to 1000.0 s in steps of 0.1
Range: 1.50 to 20.00 x FLA in steps of 0.01
Range: 1.50 to 20.00 x FLA in steps of 0.01
Range: 0.1 to 1000.0 s in steps of 0.1
Range: 1.50 to 20.00 x FLA in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled