Network Management Card (Optional) - ION F-16 User Manual

Line interactive ups 1kva/1.5kva/2kva/3kva
Table of Contents

Advertisement

Caution:
The EPO must not be connected to any utility connected circuits. Reinforced
insulation to the utility is required. The EPO Switch must have a minimum
rating of 24Vdc and 20mA and a dedicated latching-type switch not tied into
any other circuit. The EPO signal must remain active for at least 20 minutes for
proper operation
Wire Function
EPO
Note: Leave the EPO connector installed in the EPO port on the UPS even if the
EPO function is not needed.

5.3 Network Management Card (Optional)

Network Management Card allows the UPS to communicate in a variety of
networking environments and with different types of devices. The series UPS has
one available communication slot for Webpower or other optional cards to
achieve remote management of the UPS through internet/ intranet. Please
contact your local dealer for further information.
EPO Connections
Terminal Wire Size Rating
2
4-0.32mm
(12-22AWG)
EPO Connector
23
Suggested Wire Size
2
0.82mm
(18AWG)

Advertisement