Carrier 58UVB series Installation, Start-Up, And Operating Instructions Manual page 7

Direct-vent upflow variable-capacity condensing gas furnace for sizes 060-120, series 100
Hide thumbs Also See for 58UVB series:
Table of Contents

Advertisement

FACTORY-SHIPPED LOCATION
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
f. Connect larger diameter drain tube and clamp
(factory- -supplied in loose parts bag) to condensate
trap and clamp securely.
g. Route tube to coupling and cut to appropriate length.
h. Attach tube to coupling and clamp securely.
CONDENSATE TRAP(ALTERNATE LOCATION)
An alternate location for the condensate trap is the left- -hand side
of casing. (See Fig. 2 and 8.)
NOTE: If the alternate left- -hand side of casing location is used,
the factory- -connected drain and relief port tubes must be
disconnected and modified for attachment. See Condensate Trap
Tubing (Alternate Configuration) section for tubing attachment.
To relocate condensate trap to the left- -hand side, perform the
following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory- -supplied in loose
parts bag) into blower shelf hole where trap was removed.
BLOWER SHELF
CONDENSATE
TRAP (INSIDE)
ALTERNATE DRAIN
TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
1 2
1
3 4
3 4
1
WIRE TIE
GUIDES
(WHEN USED)
FRONT VIEW
Fig. 6 --- Condensate Trap
FURNACE
CONDENSATE
DOOR
TRAP
7 8
4
1 4
FIELD
26
DRAIN
CONN
SIDE VIEW
ALTERNATE LOCATION
1/ 4
OD
COLLECTOR BOX TO
TRAP RELIEF PORT
1/ 2
OD
INDUCER HOUSING
DRAIN CONNECTION
5/ 8
OD
COLLECTOR BOX
DRAIN CONNECTION
1 8
7
SCREW HOLE FOR
UPFLOW APPLICATIONS
(OPTIONAL)
7 8
1 4
2
1/ 2
-IN. PVC OR CPVC
SIDE VIEW
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Casing hole filler cap must be installed in blower shelf
hole when condensate trap is relocated to prevent
combustion products being drawn in from appliances in
the equipment room.
4. Install condensate trap into left- -hand casing hole by
inserting the top two outer tabs into casing hole, while
making sure that the larger center tab is on the outside of
the casing. Push the condensate trap up as far as possible
and then rotate the connection stubs through the hole.
Slide the condensate trap downwards to secure it in the
casing hole.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory- -supplied in loose parts bag).
CONDENSATE TRAP TUBING (ALTERNATE
CONFIGURATION)
NOTE: See Fig. 8 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain Tube
Connect collector box drain tube (blue label) to
condensate trap.
NOTE: On 17- -1/2- -in. wide furnaces ONLY, cut tube between
corrugated sections to prevent kinks.
7
FURNACE
SIDE
1 2
1
FRONT VIEW
WARNING
A06501