Proline Prowirl 73
Endress+Hauser
11.4
SPECIAL UNITS
Function descriptions for SPECIAL UNITS group
TEXT ARBITRARY
Description
VOLUME UNIT
For entering a text for a volume flow unit of the user's choice. The related time unit is
selected in the UNIT VOLUME FLOW function (ä 102).
The volume unit defined in this function is offered as a possible option (arbitrary volume
unit) in the UNIT VOLUME FLOW function (ä 102).
User input
xxxx (max. 4 characters)
Valid characters are A-Z, 0-9, +, -, decimal point, white space or underscore
Factory setting
"– – – –" (no text)
FACTOR ARBITRARY
Prerequisite
VOLUME
The function is only available if a text was entered in the TEXT ARBITRARY VOLUME
UNIT function (ä 107).
Description
For entering a quantity factor (without time) for the arbitrary volume flow unit. The
volume unit on which this factor is based is one liter.
User input
5-digit floating-point number
Factory setting
Text arbitrary volume unit / liter
TEXT ARBITRARY MASS
Description
For entering a text for a mass flow unit of the user's choice. Only the text is defined. The
associated time unit is selected in the UNIT MASS FLOW function (ä 103).
The mass unit defined in this function is offered as a possible option (arbitrary mass unit)
in the UNIT MASS FLOW function (ä 103).
Options
xxxx (max. 4 characters)
Valid characters are A-Z, 0-9, +, -, decimal point, white space or underscore.
Factory setting
"– – – –" (no text)
FACTOR ARBITRARY
Prerequisite
MASS
The function is only available if a text was entered in the TEXT ARBITRARY MASS
function (ä 107).
Description
For entering a quantity factor (without time) for the arbitrary mass flow unit. The mass
unit on which this factor is based is one kilogram.
User input
5-digit floating-point number
Factory setting
Text arbitrary mass / kg
TEXT ARBITRARY
Description
CORRECTED VOLUME
For entering a text for a corrected volume flow unit of the user's choice. The related time
unit is selected in the UNIT CORRECTED VOLUME FLOW function (ä 103).
The corrected volume unit defined in this function is offered as a possible option
(arbitrary corrected volume unit) in the UNIT CORRECTED VOLUME FLOW function.
Options
xxxx (max. 4 characters)
Valid characters are A-Z, 0-9, +, -, decimal point, white space or underscore.
Factory setting
"– – – –" (no text)
Description of device functions
107