slotshow
Displays info about which slots are occupied.
Example
switch:admin> slotshow
Slot
---------------------------------
1
2
3
4
5
6
7
8
9
10
errshow
Displays the switch error log, which lists the status of marginal/failed components. The following
example shows that the Switch 0 blower assembly has failed.
Example
sw0_155:admin> errshow
Error 15
--------
0x2e3 (fabos): Dec 29 15:57:34
Switch: 0, Error FW-BELOW1, 3, envFan001 (Env Fan 1) is below low boundary. current
value : 0 RPM. (faulty)

Replacing a Port Card or Filler Panel

This procedure provides instructions on how to remove and replace port cards (see
page
3-7) and filler panels (see
following steps should be taken before removing/replacing a port card:
1.
Check the LEDs.
The LEDs are located on the front panel of each port card (see
Table 2-1 on page 2-6
Note:
2.
Establish a telnet/console session.
Before replacing a port card, establish a telnet/console connection to determine a failure and verify
operation after replacement. Refer to the Fabric OS Procedures Guide for information about how to
check the status of hardware components using command line interface.
SilkWorm 12000 Hardware Reference Manual
Blade Type
ID
Status
SW BLADE
2
FAULTY
SW BLADE
2
DISABLED
SW BLADE
2
ENABLED
SW BLADE
2
DIAG RUNNING POST2
CP BLADE
1
ENABLED
CP BLADE
1
ENABLED
UNKNOWN
VACANT
SW BLADE
2
DIAG RUNNING POST1
SW BLADE
2
INSERTED, NOT POWERED ON
UNKNOWN
VACANT
Figure 3-2 on page
for a description of the port card LEDs.
The WWN bezel on the non-cable side of the SilkWorm 12000 also displays a power and
status LED for each port card.
Maintaining the SilkWorm 12000
3-10) from the SilkWorm 12000 switch. The
Figure 2-1 on page
3
Figure 3-1 on
2-5). Refer to
3-5