Fault
Cause
F00072
USS setpoint fault
F00090
Encoder feedback loss
F0395
The fault occurs after a CU/PM swap or
startup clone. It can also be cause by a
faulty read from the EEPROM.
Alarm
Meaning
A0700
Correct the PROFIBUS configuration
A0702
Check connector, cable and PROFIBUS
master.
A0703
Check setpoints from the PROFIBUS
master. Switch SIMATIC CPU to "RUN".
A0704
Activate internode transmitter.
A0705
None (fault is with the inverter).
A0706
None diagnostic parameter r2041.
A0710
Communication interface on Control Unit
may be broken.
A0711
Check P0918 address and P2041.
CU240E
Getting Started, 10/2007, A5E01301680B AA
Remedy
Check USS master
Check that the encoder is installed and
commissioned correctly.
The parameter or configuring settings by the
PROFIBUS master are invalid.
The link to the PROFIBUS is interrupted.
No setpoints or invalid setpoints (control
word = 0) are being received from the
PROFIBUS master.
At least one configured internode transmitter
is not yet active, or has failed.
No actual values received from inverter.
PROFIBUS DP software error.
Inverter has detected failure of PROFIBUS
communications link.
Invalid value of PROFIBUS parameter.
Diagnostics
29