● Before working in this unit, isolate it from the power supply.
● Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate requirement
of the local wiring code.
Observe the notes mentioned below when wiring to the terminal block.
Precautions to be taken for power supply wiring.
(Use a round crimp-style terminal for connection to the terminal block.
In case it cannot be used due to unavoidable reasons, be sure to
observe the following instruction.)
● When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
Stripping wire at terminal block
● Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
● Transmission wire must be routed at least 50mm away from the power cable.
● Transmission wire should be a shielded wire.
10
Compressor
Compressor
Maximum
Full Load
Continuous
Current,
Current (A)
FLA (A)
15
8
20
11
15/15
8/8
19/19
10/10
20/20
11/11
23/23
13/13
25/25
15/15
35/35
19/19
Strip wire end
to this point.
Good
Compressor
Locked Rotor
Current,
LRA (A)
64
101
64/64
100/100
101/101
128/128
139/139
140/140
WARNING
Round crimp-style
terminal
CAUTION
Excessive strip length
may cause electrical
shock or leakage.
Wrong
WARNING
Minimum
Maximum
Circuit Amps,
Fuse Amps,
MCA (A)
MFA (A)
13.7
20.0
19.2
32.0
25.0
32.0
32.2
40.0
35.7
50.0
38.9
63.0
43.9
63.0
53.6
80.0
Stranded wire