Troubleshooting Diagnostics - Ferroli BLUEHELIX TECH S 45H Instructions For Use, Installation And Maintenance

Hide thumbs Also See for BLUEHELIX TECH S 45H:
Table of Contents

Advertisement

BLUEHELIX TECH S 45H
Proceed in reverse order to refit the front panel. Make sure it is correctly hooked to the
upper fastenings and is correctly positioned at the sides. When tightened, the head of
screw "A" must not be below the lower fold (see fig. 25).
OK
fig. 25 - Correct position of front panel
Periodical check
To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly inspection, providing for the following checks:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly
The fume exhaust circuit must be perfectly efficient
The sealed chamber must be tight
The air-fume end piece and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits For possible cleaning
do not use chemical products or wire brushes
The electrode must be properly positioned and free of scale
The gas and water systems must be tight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables
The condensate evacuation system must be efficient with no leakage or obstruc-
tions
The trap must be full of water.
4.4 Troubleshooting
Diagnostics
In case of operation faults or problems, the display flashes and the fault identification
code appears.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the reset button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 8 - List of faults
Fault
Fault
Possible cause
code
No gas
Ignition/detection electrode fault
A01
No burner ignition
Faulty gas valve
Insufficient gas supply pressure
Trap blocked
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature
A03
protection intervention
No water circulation in the system
Air in the system
Fume extraction duct safety
Fault F07 generated 3 times in the
A04
device intervention
last 24 hours
Fault F15 generated for 1 hour
A05
Fan protection activated
(consecutive)
Fault
code
NO
Cure
Check the regular gas flow to the
boiler and that the air has been
eliminated from the pipes
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Check the gas valve and replace it if
necessary
Check the gas supply pressure
Check the trap and clean it if
necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and
operation of the heating sensor
Check the circulating pump
Vent the system
See fault F07
See fault F15
cod. 3541G102 - Rev. 0
Fault
Possible cause
Ionisation electrode fault
Flame unstable
Gas valve Offset fault
No flame after ignition stage
A06
(6 times in 4 minutes)
air/fume ducts obstructed
Trap blocked
The fume probe detects an excessive
F07
High fume temperature
temperature
Sensor damaged
F10
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Sensor damaged
F11
Return sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F12
DHW sensor fault
Wiring shorted
Wiring disconnected
Probe damaged
F13
Fume probe fault
Wiring shorted
Wiring disconnected
Sensor damaged
F14
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
No 230V power supply
F15
Fan fault
Tachometric signal interrupted
Fan damaged
F34
Supply voltage under 170V Electric mains trouble
F35
Faulty mains frequency
Electric mains trouble
Pressure too low
Incorrect system water
F37
Water pressure switch damaged or
pressure
not connected
Probe damaged or wiring shorted
F39
External probe fault
Probe disconnected after activating
the sliding temperature
A41
Sensor positioning
Heating sensor detached from pipe
A44
A42
Heating sensor fault
Sensor damaged
No system H
Exchanger protection inter-
F43
vention.
Air in the system
F52
Heating sensor fault
Sensor damaged
A61
Controller ABM03C fault
Controller ABM03C internal error
No communication between
Controller not connected
A62
electronic controller and
Valve damaged
gas valve
A63
F64
Controller ABM03C fault
Controller ABM03C internal error
A65
F66
A23
A24
F20
F21
Card parameter fault
Wrong card parameter setting
A26
F40
F47
- 0 /2016
Cure
Check the position of the ionisation
electrode and replace it if necessary
Check the burner
Check the Offset adjustment at
minimum power
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Check the trap and clean it if
necessary
Check the exchanger
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the fume
probe
Check the wiring or replace the sensor
Check the 3-pin connector wiring
Check the 5-pin connector wiring
Check the fan
Check the electrical system
Check the electrical system
Fill the system
Check the sensor
Check the wiring or replace the sensor
Reconnect the external probe or
disable the sliding temperature
Check the correct positioning and
operation of the heating sensor
Replace the sensor
O circulation
Check the circulating pump
2
Vent the system
Replace the sensor
Check the earth connection and
replace the controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the earth connection and
replace the controller if necessary.
Check the card parameter and modify
it if necessary.
EN
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents