20
en | Configuration
Default: 0.0.0.0
Selections: 0.0.0.0 to 255.255.255.255
If the IP communicator fails to get an address from the primary server, it tries the alternate
DNS server. Enter the IP address for the alternate IPv4 DNS server.
Modem Reset Count
Default: 5
Selections: 0 to 99
This parameter sets the number of times a data packet must be sent without a reply before
the cellular module modem resets.
When connected to an SDI2 control panel v2.03 or higher, the default is zero and controlled
by the above mentioned control panel, unless control panel programming is disabled.
Web/USB access enable
Default: No
Selections: Yes/No
This parameter enables authorized users to view and modify the module configuration
parameters through a standard web browser or USB, depending on available options.
Notice!
Do not disable for some control panels
Do not disable USB access unless you are on an SDI2 control panel or AMAX 2100/ 3000/
4000 with Panel Programming Enable enabled. With SDI and other option control panels, you
must use the USB interface.
Web Access Password
Default:  B42V2
Selections: blank, ASCII printable characters
This parameter sets the password required to log in for web access.
The password must be 4-10 ASCII printable characters in length. Blank spaces disable the
password checking.
TCP Keep Alive Time
Default: 45
Selections: 0 - 65 (seconds)
Time in seconds between TCP keep-alive messages. Keep alive messages make sure that a
connection stays active.
Reporting Delay for No Towers (sec)
Default: 0
Selections: 0 (disabled) - 3600 (seconds)
When the cellular plug-in module senses no towers for the seconds set by this parameter, the
control panel records a No Towers event and a No IP Address event.
The control panel records a No Tower restoral event when the cellular plug-in module senses
one or more towers for the seconds set by this parameter.
The control panel records a No IP Address restoral event when the cellular plug-in module
registers with one or more towers and receives an IP address within 60 seconds.
Reporting Delay for Single Tower (sec)
Default: 1800
2017.10 | 09 | F.01U.300.740