Suction Temperature Sensor Breakaway Error - Samsung AM045NN4DEH Series Service Manual

System airconditioner, indoor unit
Hide thumbs Also See for AM045NN4DEH Series:
Table of Contents

Advertisement

4-4-47

: Suction Temperature sensor breakaway error

Outdoor unit display
Indoor unit display
∙ If the suction temperature right before operating the Comp, when the operating order is highest, is set at Tsuc, ini,
Criteria
Cause of problem
∙ Suction temperature sensor breakaway/defective.
1. Cause of problem
and sensor Holder accurately
resistance value reasonable?
Samsung Electronics
and the suction temperature of the current Comp is set at Tsuc, real, it is considered to have an error if the condition
of Tsuc, real < Tsuc,ini| < 2°C is maintained for 30 minutes.
Is Suction sensor
attached?
Yes
Is Suction sensor
(Refer to E231 )
Yes
Complete
Operation
Timer
No
No
Troubleshooting
Re-insert the sensor.
Re-attach the sensor holder.
Defective Sensor : Replace Sensor