Error On Suction Temperature Sensor (Short Or Open). (E-308) - Samsung AM053FXMDCH Service Manual

System air conditioner
Hide thumbs Also See for AM053FXMDCH:
Table of Contents

Advertisement

3-11. Error on suction temperature sensor. (Short or open) (E-308)
Outdoor unit Display
Indoor unit Display
Judgement Method
Cause of problem
connector for the Liquid Pipe
Temperature sensor break away
from the PCB?
Separate the connector of the Liquid Pipe
Temperature sensor from the PCB and measure
the resistance value between the 2 terminals.
Did the resistance
value signicantly stray from
the following temperature
Restart operation after replace the PCB.
44
Operation
Operation
Operation
Did the
Yes
table?
Yes
E-308
Duct, Cassette (1 / 2Way), Console, Ceiling
Defrost
Timer
×
×
Cassette (4Way / Mini 4Way)
Defrost
Timer
×
Duct, Cassette (1/2 Way), Console, Ceiling
Timer
Turbo
×
×
: ON
: Flash ×: OFF
※ ●
No
Restart operation after connecting
No
Replace this part as it is the defective
of the liquid pipe temperature sensor itself.
Temperature(°C)
70
60
50
40
30
20
10
0
-10
Fan
Filter / MPI
×
Filter
×
24°C
27°C
×
the connector to PCB.
Resistance(KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Samsung Electronics