Troubleshooting
4-4-45
: Suction Temperature sensor breakaway error
Outdoor unit display
Indoorunit display
×(Operation)
∙ If the suction temperature right before operating the Comp, when the operating order is highest, is set at Tsuc, ini,
Judgment Method
Cause of problem
∙ Suction temperature sensor breakaway/defective.
1. Cause of problem
and sensor Holder accurately
resistance value reasonable?
4-80
(Reservation)
and the suction temperature of the current Comp is set at Tsuc, real, it is considered to have an error if the condition of Tsuc,
real < Tsuc,ini| < 2°C is maintained for 30 minutes.
Is Suction sensor
attached?
Yes
Is Suction sensor
(Refer to E231 )
Yes
Complete
(Blast)
(Filter) ×(Defrost)
No
No
Re-insert the sensor.
Re-attach the sensor holder.
Defective Sensor : Replace Sensor