Generator Shut-Down Procedures - MQ Power DCA25SSIU4F Operation Manual

Whisperwatt series 60hz generator isuzu 4le2t diesel engine
Hide thumbs Also See for DCA25SSIU4F:
Table of Contents

Advertisement

WARNING
NEVER stop the engine suddenly except in an
emergency.
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 47 to the OFF position.
Figure 47. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the Auto Off/Reset Manual Switch (Figure 48)
in the OFF/RESET position.
Auto Off/Reset Manual
Figure 48.
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
DCA25SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #4 (01/17/18) — PAGE 33

GENERATOR SHUT-DOWN PROCEDURES

Switch
EMERGENCY SHUTDOWN PROCEDURE
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 47 to the OFF position.
AUTOMATIC SHUT-DOWN SYSTEM
This unit is equipped with safety devices to automatically
stop the engine in the event of low oil pressure, approximately
14 psi (97 kPa), or high water temperature, approximately
212° F (100° C), overspeed approximately +15%. The alarm
lamps on the ECU illuminate to signify the reason for the
shutdown.
NOTICE
Before inspecting generator, check that the Auto/
Manual switch is in the OFF/RESET position, and place
all circuit breakers in the OFF position. Allow sufficient
time for adequate cooling. When ready to restart,
complete all steps in the Generator Startup Procedure
section of this manual.