10.
Terminals are UL and CSA rated at 90˚C. Refer to Tables K and L for power cable
terminations, and Table M and N for conduit requirements. Drawing 164201409---6 shows
the location of the power cable terminals inside the Parallel Cabinet.
Table K. Powerware BPIV Parallel Cabinet Power Cable Terminations
Terminal Function
AC Input from Each
p
UPM
AC Input To Bypass
p
yp
AC Output to Critical
p
Load
Customer Ground
Table L. Powerware BPIV Parallel Cabinet Power Cable Terminations
Terminal Function
AC Input from Each
p
UPM
AC Input To Bypass
p
yp
AC Output to Critical
p
Load
Customer Ground
NOTE: Customer ground can be
run in any conduit listed in
Tables M and N.
A ---8
15 kVA 1+1, 2+0, 2+1, 3+0, and 3+1 Configuration
30 kVA 1+1, 2+0, and 2+1 Configurations
Size of Pressure
Terminal
Function
E1
Phase A
1 --- #8---#2/0
E2
Phase B
1 --- #8---#2/0
E3
Phase C
1 --- #8---#2/0
E12
Neutral
1 --- #8---#2/0
Frame
Ground
4 --- #14---#1/0
Ground
E6
Phase A
1 --- #6---500 kcmil
E7
Phase B
1 --- #6---500 kcmil
E8
Phase C
1 --- #6---500 kcmil
3E12
Neutral
1 --- #6---500 kcmil
E9
Phase A
1 --- #6---500 kcmil
E10
Phase B
1 --- #6---500 kcmil
E11
Phase C
1 --- #6---500 kcmil
3E12
Neutral
1 --- #6---500 kcmil
Frame
Ground
4 --- #14---#1/0
Ground
30 kVA 3+0 and 3+1 Configurations
Size of Pressure
Terminal
Function
E1
Phase A
1 --- #8---#2/0
E2
Phase B
1 --- #8---#2/0
E3
Phase C
1 --- #8---#2/0
E12
Neutral
1 --- #8---#2/0
Frame
Ground
4 --- #14---#1/0
Ground
E6
Phase A
4 --- #14---#2/0
E7
Phase B
4 --- #14---#2/0
E8
Phase C
4 --- #14---#2/0
3E12
Neutral
6 --- #14---#2/0
E9
Phase A
4 --- #14---#2/0
E10
Phase B
4 --- #14---#2/0
E11
Phase C
4 --- #14---#2/0
3E12
Neutral
6 --- #14---#2/0
Frame
Ground
8 --- #14---#1/0
Ground
Tightening Torque
Termination
N-M (lb-in.)
12.4(110)
12.4(110)
12.4(110)
20.3(180)
5.6(50)
56.5(500)
56.5(500)
56.5(500)
56.5(500)
56.5(500)
56.5(500)
56.5(500)
56.5(500)
5.6(50)
Tightening Torque
Termination
N-M (lb-in.)
12.4(110)
12.4(110)
12.4(110)
20.3(180)
5.6(50)
20.3(180)
20.3(180)
20.3(180)
20.3(180)
20.3(180)
20.3(180)
20.3(180)
20.3(180)
5.6(50)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201409---1
REVISION:
B
Powerware BPIV Parallel Cabinet Installation and Operation
Type
Screw
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
Slotted
1/2 Allen
1/2 Allen
1/2 Allen
1/2 Allen
1/2 Allen
1/2 Allen
1/2 Allen
1/2 Allen
Slotted
Type
Screw
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
Slotted
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
3/16 Allen
Slotted
SHEET:
7 of 11
DATE:
101503
164201409 REV. B
101503