Appendix F: PX3 Models with Residual Current Monitoring
config:#
residualCurrentMonitor <n> criticalRatedResidualOperatingCurrent <value>
600

Showing Residual Current Monitor Information

This command syntax shows the residual current monitoring (RCM)
information, which is only available on the models with RCM. The
information displayed include the RCM current, state and thresholds.
#
show residualCurrentMonitor <n>
Variables:
<n> is one of the options:
Option
Description
all
Displays the RCM information of all inlets.
Tip: You can also type the command without
adding this option "all" to get the same data.
A specific inlet
Displays the RCM information of the specified inlet
number
only.
An inlet number needs to be specified only when
there are more than 1 inlet on your PDU.

Setting RCM Current Thresholds

Warning Rated Residual Operating Current is the upper warning
threshold of the PX3 RCM sensor, and Critical Rated Residual Operating
Current is the upper critical threshold of the RCM sensor. These
thresholds are set in the configuration mode. See
Configuration Mode
(on page 403).
Note: A residual current sensor's LOWER warning and LOWER critical
thresholds do NOT affect the operations of the RCM state sensor so you
can ignore them.
To configure the RCM's Critical level:
Note: The PX3 triggers events when residual current values are above
(but not equal to) thresholds. For example, you would set the critical
threshold to 29mA to specify the IEC 62020 IΔn of 30mA. See
Compliance with IEC 62020
To configure the RCM's Warning level:
all
, or a number.
Entering
(on page 590).