And 10" Hp Protectus Iii Turbine Elements Performance Specifications - Neptune TRICON E Installation And Maintenance Manual

Table of Contents

Advertisement

Compound Meter
Size and Type
1
3"TRU/FLO
4"TRU/FLO
6"TRU/FLO
2" HP TRU/FLO
4" PROTECTUS III
6" PROTECTUS III
8" PROTECTUS III
10" PROTECTUS III
4" HP PROTECTUS III
6" HP PROTECTUS III
8" HP PROTECTUS III
10" HP PROTECTUS III
1
For TRICON/E Performance Specifications of Compound Meters, refer to the specification information of each respective meter element.
Refer to Table 3.10 for the performance specifications of the 4", 6", 8", and 10" HP PROTECTUS III Turbine Elements.
2
Table 3.10 4", 6", 8", and 10" HP PROTECTUS III Turbine Elements Performance Specifications
METER SIZE
MAXIMUM CONTINUOUS
(in)
FLOW RATE (gpm)
4
1,200
6
2,500
8
4,000
10
6,500
For the High Resolution Output of the TRICON/E2 transmitters, multiply these values by 9 and for the TRICON/E3, multiply these values by 10.
1
2
Note: This table is based on mounting HPT TRICON/E3 on the same size HP PROTECTUS III Turbine Element.
TRICON/E/E2/E3 TRANSMITTER INSTALLATION AND MAINTENANCE GUIDE
Table 3.9 Compound Meters
Turbine Element
3" TT
4" TT
6" TT
2" HPT
4" TT
6" TT
8" TT
10" TT
2
2
2
2
NUMBER OF PULSES
PER GALLON
1
@ MAXIMUM FLOW RATE (Hz)
7.5560
0.7556
0.6095
0.5333
Disc Element
" T-10
5
8
" T-10
3
4
1" T-10
" T-10
5
8
1" T-10
1
" T-10
1
2
2" T-10
2" T-10
1" T-10
1
" T-10
1
2
2" T-10
2" T-10
PULSE OUTPUT
FLOW RANGE OF 4-20MA
1
151.2
37.78
40.63
57.78
2
OUTPUT (gpm)
0 – 1,200
0 – 2,888
0 – 4,959
0 – 9,209
3-4