Notes On Replacing The Parts - Mitsubishi Electric EHSE-YM9EC Service Manual

Hydrobox
Table of Contents

Advertisement

Notes on replacing the parts

Replacement of the parts listed below requires the following procedure.
After the parts are removed, eliminate loctite on threads by applying loctite remover, apply new loctite, and then install and tighten the parts to the specified
tightening torques below. For details about recommended loctite and loctite remover, refer to Table 11-1, and for details about the replacement parts and
their tightening torques, refer to Table 11-2.
Table 11-1
Recommended
Manufacturer
Loctite
Henkel
Loctite remover
Henkel
Note: When using the products above, refer to the appropriate manuals that come with the individual products.
Table 11-2
1
Part name *
PRESSURE RELIEF VALVE 3bar
1
*
For more details about the listed parts, refer to the parts catalogue.
2
*
Undertightening and overtightening the parts affect water seal life. Tighten the parts to the appropriate tightening torques.
When installing the parts that are not listed above, observe the tightening torques in accordance with Table 11-3.
Always use a new O-ring or gasket.
Table 11-3
Size
[inch]
G1/4"
Gasket
G1 1/2"
Strainer cover
O-ring
Air vent (Automatic)
Drain cock (primary circuit)
Attached packing
Flare joint
Booster heater
After the procedure is complete, ensure that no water leaks.
OCH590B
No.
Loctite 577
Loctite 7200 Gasket Remover
Recommended tightening
2
torque [Nm] *
15 ± 1
Recommended tightening torque
[Nm]
8 ± 1
42 ± 2
45 ± 2
15 ± 1
0.25 ± 0.05
35 ± 2
71
Note
Apply loctite all over from the end of external thread to the second
ridge. After installing the parts, fix the parts for at least 30 minutes
Spray loctite remover over sealant on the threads, let the sealant
sit until soft, and then eliminate it with a wire brush.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents