No.
Fault symptom
14
In 2-zone tempera-
1.
When Zone1 and Zone2 are both in heating
ture control, only
mode, the hot water temperature in Zone2
Zone2 does not
does not exceed that in Zone1.
reach the set tem-
2.
Faulty wiring of motorized mixing valve
perature.
3.
Faulty installation of motorized mixing valve
4.
Incorrect setting of Running time
5.
Motorized mixing valve failure
15
After DHW operation
At the end of the DHW mode operation the 3-way
room temperature
valve diverts hot water away from the DHW circuit
rises slightly.
into space heating circuit.
This is done to prevent the hydrobox components
from overheating.
The amount of hot water directed into the space
heating circuit varies according to the type of the
system and of the pipe run between the plate heat
exchanger and the hydrobox.
16
The room tempera-
3-way valve failure
ture rises during DHW
operation.
17
Water discharges
1. If continual – pressure relief valve may be
from pressure relief
damaged.
valve.
(Primary circuit)
2. If intermittent – expansion vessel charge may
have reduced/bladder perished.
18
Water discharges
1. If continual – field supplied pressure reducing
from pressure relief
valve not working.
valve (field supplied
2. If continual – pressure relief valve seat may
item).
be damaged.
(Sanitary circuit)
3. If intermittent – expansion vessel charge may
have reduced/bladder perished.
4. DHW tank may have subjected to backflow.
19
Noisy water circula-
Air in water circulation pump
tion pump
20
Noise during hot
1.
Loose airing cupboard pipework
water draw off
typically worse in the
2.
Heaters switching ON/OFF
morning.
21
Mechanical noise
1.
Heaters switching ON/OFF
heard coming from
the hydrobox.
2.
3-way valve changing position between DHW and
heating mode
22
Water circulation
Water circulation pump jam prevention mechanism
pump runs for a
(routine) to inhibit the build-up of scale
short time unexpect-
edly .
23
Milky/Cloudy water
Oxygenated water
(Sanitary circuit)
24 Heating mode has
The time of "Delay" set in "Economy settings
for pump" is too short. (Go to "Service menu"
been on standby for
→ "Auxiliary settings" → "Economy settings for
a long time (does
pump").
not start operation
smoothly).
25 The hydrobox that
The hydrobox is designed to run in an operation
mode with a higher priority (i.e. DHW mode in this
was running in the
case) at power recovery.
heating mode before
power failure is
running in the DHW
mode after power
recovery.
OCH590B
Possible cause
51
Explanation - Solution
1.
Normal action
No action necessary
2.
Refer to "5.3 Wiring for 2-zone temperature control" in installation manual.
3.
Check for correct installation. (Refer to the manual included with each mo-
torized mixing valve.)
4.
Check for correct setting of Running time.
5.
Inspect the mixing valve. (Refer to the manual included with each motorized
mixing valve.)
• Normal operation
• No action necessary
Check the 3-way valve.
1. Turn the handle on the pressure relief valve to check for foreign objects in it.
If the problem is not still solved, replace the pressure relief valve with a new
one.
2. Check pressure in expansion vessel.
Recharge to 1 bar if necessary.
If bladder perished replace expansion vessel with a new one.
1. Check function of pressure reducing valve and replace if necessary.
2. Turn the handle on the pressure relief valve to check for foreign objects
inside. If the problem is not still solved, replace the pressure relief valve.
3. Check gas-side pressure in expansion vessel.
Recharge to correct precharge pressure if necessary.
If bladder perished replace expansion vessel with a new one with appropriate
pre-charge.
4. Check the pressure in DHW tank. If pressure in DHW tank is similar to that in
the incoming mains, cold water supply that merges with incoming mains wa-
ter supply could flow back to DHW tank. Investigate source of back-feed and
rectify error in pipework/fitting configuration. Adjust pressure in cold supply.
Use manual and automatic air vents to remove air from system.
Top up water if necessary to achieve 1 bar on primary circuit.
1. Install extra pipe fastening clips.
2. Normal operation
No action necessary
• Normal operation
• No action necessary
• Normal operation
• No action necessary
Water from any pressurised system will release oxygen bubbles when water is
running. The bubbles will settle out.
Increase the time of "Delay" in "Economy settings for pump".
• Normal operation
• A fter the DHW max. operation time has elapsed or the DHW max. temperature
has been reached, the DHW mode switches to the other mode (ex. Heating
mode).