DISASSEMBLY PROCEDURE

14. How to detach and attach the different diameter quick joint

Refer to the following steps when detaching and attaching the
different diameter quick connection.
(1) Remove the clip. (Photos 14-1 and 14-2)
(2) S eparate the connected parts to remove the O-ring. (Photo
14-3)
• Do not reuse the removed O-ring.
• W ipe off if dirt or foreign matters are found on the sealing
surface where the O-ring touches.
(3) A pply grease on the O-ring using a plastic bag, etc. (Photo
14-4)
(4) A ttach the O-ring to the male part of quick connection. (Pho-
to 14-5)
• Keep the O-ring free from dirt or foreign matters.
(5) C onnect the male and female parts of the quick connection.
(Photo 14-5)
(6) Attach the clip. (Photo 14-6)
• E nsure to attach the wider diameter of the clip to the fe-
male side. Failure to do so, it may cause water leak at the
connected part. (Photo 14-7)
Photo 14-3
Male
Female
Photo 14-6
OCH590B
Photo 14-4
O-ring
Photo 14-7
Clip
PHOTOS
Photo 14-1
Photo 14-2
Photo 14-5
Plastic
bag
O-ring
Gap
70
Clip
Clip
Male
Female