Compliance With The European Machinery Directive - ABB ACS880-17 Hardware Manual

132...400 kw, 200...450 hp
Hide thumbs Also See for ACS880-17:
Table of Contents

Advertisement

200 The Safe torque off function
Standard
IEC 61326-3-1:2008
IEC 61508-1:2010
IEC 61508-2:2010
IEC 61511-1:2016
IEC 61800-5-2:2016
EN 61800-5-2:2007
IEC 62061:2015
EN 62061:2005
+AC:2010+A1:2013+A2:2015
EN ISO 13849-1:2015
EN ISO 13849-2:2012
The function also corresponds to Prevention of unexpected start-up as specified by
EN 1037:1995 + A1:2008 and Uncontrolled stop (stop category 0) as specified in
EN 60204-1.

Compliance with the European Machinery Directive

See section
Compliance with the European Machinery Directive
Wiring
The following diagrams present examples of Safe torque off wiring for
a single drive (page 202)
multiple drives (page 203)
multiple drives when an external 24 V DC power supply is used (page 204).
For information on the specifications of the STO input, see chapter
R11
(page 113).
Activation switch
In the wiring diagrams below, the activation switch has the designation [K]. This represents
a component such as a manually operated switch, an emergency stop push button switch,
or the contacts of a safety relay or safety PLC.
If a manually operated activation switch is used, the switch must be of a type that can
be locked out to the open position.
The contacts of the switch or relay must open/close within 200 ms of each other.
An FSO-xx safety functions module or an FPTC-0x thermistor protection module can
also be used. For more information, see the FSO-xx module documentation.
Name
Electrical equipment for measurement, control and laboratory use – EMC
requirements – Part 3-1: Immunity requirements for safety-related
systems and for equipment intended to perform safety-related functions
(functional safety) – General industrial applications
Functional safety of electrical/electronic/programmable electronic safety-
related systems – Part 1: General requirements
Functional safety of electrical/electronic/programmable electronic safety-
related systems – Part 2: Requirements for
electrical/electronic/programmable electronic safety-related systems
Functional safety – Safety instrumented systems for the process industry
sector
Adjustable speed electrical power drive systems –
Part 5-2: Safety requirements – Functional
Safety of machinery – Functional safety of safety-related electrical,
electronic and programmable electronic control systems
Safety of machinery – Safety-related parts of control systems – Part 1:
General principles for design
Safety of machinery – Safety-related parts of control systems – Part 2:
Validation
on page 176.
Control unit of frame

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-37