Drive I/O, I/O extension and encoder interface modules

See
section
AI1 and AI2 as Pt100, Pt1000, PTC and KTY84 sensor inputs (XAI, XAO)
page
116
section
DI6 (XDI:6) as PTC sensor input
FPTC-01 thermistor protection module (option +L536) for ACS880 drives user's
manual (3AXD50000027750 [English])
FPTC-02 ATEX-certified thermistor protection module Ex II (2) GD (option
+L537+Q971) for ACS880 drives user's manual (3AXD50000027782 [English]).
This table shows what temperature sensor types you can connect to the drive I/O
extension modules as well as the insulation requirement for the sensor.
Extension module
Type
Insulation/Isolation
FIO-11
Galvanic isolation between sensor
connector and other connectors
(including drive control unit connector)
FEN-xx
Galvanic isolation between sensor
connector and other connectors
(including drive control unit connector)
FAIO-01 Basic insulation between sensor
connector and drive control unit
connector. No insulation between
sensor connector and other IO
connectors.
FPTC-
Reinforced insulation between sensor
xx
connector and other connectors
(including drive control unit
connector).
Note: The inaccuracy of the drive analog inputs for Pt100 sensors is 10 °C (50 °F). If a
better accuracy is needed, use the FAIO-01 analog I/O extension module (option +L525).
Guidelines for planning the electrical installation 87
on
page117
Temperature sensor
type
PTC
KTY
Pt100,
Pt1000
-
X
X
X
X
-
X
X
X
X
-
-
Temperature sensor
insulation requirement
Reinforced insulation
Reinforced insulation
Basic insulation. Connectors
of extension module other
than sensor connector must
be left unconnected.
No special requirement