Ericsson RBS 2106 Hardware Reference Manual page 93

Gsm system
Hide thumbs Also See for RBS 2106:
Table of Contents

Advertisement

RBS 2206
There are two ways to connect power to the base station. They are:
Note:
Table 9
Voltage range for specified
Performance (phase voltage)
Voltage range
Frequency
Inrush current, max.
Maximum AC power
Non-destructive range
Overvoltage <20 ms
Maximum ground leakage current
1)
2)
EN/LZT 720 0225 R3A
Single phase line to neutral.
Single phase line to line.
When single phase line to line is used, each PSU requires two circuit
breakers.
AC mains power requirements
90 – 108 V AC with reduced output power. 1000 W per PSU
Install external filter and stabiliser if not met.
120 – 250 V AC
(1)
108 – 275 V AC
45 – 65 Hz
30 A (1 – 30 ms)
1.4 kW x 4
0 – 275 V AC
(2)
325 V
10 mA x 4
Radio Base Station
19 (24)