Ericsson RBS 2106 Hardware Reference Manual page 71

Gsm system
Hide thumbs Also See for RBS 2106:
Table of Contents

Advertisement

RBS 2106
7.4
Power Consumption
Table 14 Power consumption
Climate system
Heater plus forced-air
cooling only
Heater plus
refrigerated cooling
8
Transmission
The RBS 2106 supports two transmission standards:
9
External Alarms
The RBS 2106 supports a maximum of 16 external alarms. The external alarm
device can set the alarm by either an open or a closed condition.
The alarm device connected to the screw terminals should be isolated relay
contacts. A closed contact (logic zero) is required to be below 2 kΩ, and an
open contact (logic one) above 100 kΩ. The current through a closed 0 Ω
contact is 1.2 mA. The voltage between terminals with an open contact is 24 V
DC.
The external alarms are defined at the installation. They are defined by using
the Operation and Maintenance Terminal (OMT) or from the BSC using the
remote OMT.
10
Standards, Regulations and Dependability
In this section a brief overview over standards, type approval and
electromagnetic compatibility are stated.
10.1
Safety Standards
In accordance to the market requirements, the RBS 2106 complies with the
following product safety standards:
EN/LZT 720 0222 R3A
T1 1.5 Mbit/s, 100 Ω, with internal synchronisation
E1 2 Mbit/s, 75 Ω, with PCM synchronisation
E1 2 Mbit/s, 120 Ω, with PCM synchronisation
73/23/EEC Low voltage directive
Power consumption,
input voltage >200 V
AC
5948 W
6588 W
Radio Base Station
Power consumption,
input voltage < 120 V
AC
6049 W
6049 W
27 (30)