Radio Base Station
Layout for RBS Cabinets
BBS
Unit of measurement: mm
Figure 2 Floor layout and space requirements
The RBS cabinets and BBS racks are mounted on the floor, and may be
positioned against a wall, back to back, or free standing without contact with
other cabinets.
Expansion cabinets and racks can be positioned to the left or to the right of the
master cabinet. However, expansion to the right is recommended in order to
follow the same standard globally.
A distance of 1000 mm in front of the cabinets and racks for maintenance
work is recommended.
Note:
Earthquake Requirements
If the RBS cabinet shall fulfill the requirements for earthquake protection, the
space between wall and cabinet is to be at least 100 mm and between
cabinets at least 150 mm.
6 (24)
Space for future expansion must be considered as indicated in the
dotted line in the figure above.
RBS
RBS
o
a=130
RBS 2206
RBS
P007781A