Figure 6. Line Set Sizes - EarthLinked AVS-0030-A Quick Start Instructions

Classic series sd (h) geothermal heating and cooling system
Table of Contents

Advertisement

The compressor unit package contains a service valve kit and an adapter kit. The two service
valves are to be installed on the earth loop vapor and liquid connections of the compressor
unit, using the adapters to right-size to the proper earth loop line set.
Installation of the service valves will provide isolation of the earth loop system from the compressor
unit and provide easy access to the refrigerant system.
For the installation of system components requiring refrigeration connections, refer to Figure 6 for line
set sizes and the appropriate installation manual(s) following Figure 6.
LINE SET ADAPTERS REQUIRED FOR THE AIR HANDLER, CASED COIL, HYDROINIC
WATER MODULE AND DOMESTIC WATER MODULE ARE FIELD SUPPLIED. CHECK ALL
APPROPRIATE COMPRESSOR UNIT STUB-OUT TUBING SIZES FOR REQUIRED FIELD
SUPPLIED ADAPTERS!
EARTHLOOP, AIR HANDLER, CASED COIL LINE SETS
COMPRESSOR
UNIT SIZE
2.0 Tons (-024)
2.5 Tons (-030)
3.0 Tons (-036)
3.5 Tons (-042)
4.0 Tons (-048)
4.5 Tons (-054)
5.0 Tons (-060)
*Liquid and Vapor lines must BOTH be insulated with Armaflex® or equivalent with at least 1/2" wall thickness for the full
length of the line set.
Series SV Service Valve and ADK Adapter Kit
Series AVS Air Handler
Series CCS Cased Coil
SD Series Heating Option Kit, SDHO-1872
Series HWM Hydronic Water Module
Series HCM Hybrid Cooling Module
DIRECT AXXESS
After installing and nitrogen brazing the HVAC system components and compressor unit service
valves, turn the Service Valves to Full Open and pressurize the refrigeration system to 150 psig with
dry nitrogen and a trace of refrigerant. Valve off the nitrogen Tank from the HVAC system
components and check joints with a sensitive Electronic Leak Detector to ensure they are sealed.
Repair any leaks and re-test as appropriate.
SD-410-QS (H) (06/15)
LINE SET O.D., INCHES
LIQUID*
VAPOR*
3/8
5/8
3/8
3/4
1/2
3/4
1/2
3/4
1/2
7/8
1/2
7/8
1/2
7/8

Figure 6. Line Set Sizes

®
Earth Loop Specification and Installation Manual
HWM LINE SETS
LINE SET O.D., INCHES
HWM
MODEL
LIQUID*
-024C
3/8
-030C
3/8
-036C
3/8
-042C
1/2
-048C
1/2
-054C
1/2
-060C
1/2
VAPOR*
1/2
1/2
1/2
5/8
5/8
3/4
3/4
Page 12