Battery information and settings:
ABM charging cycling disable
Charging temp compensation
Battery size setting
Number of 36 pcs. battery strings
Battery low alarm level
Automatic battery support test
Maximum charging current
Output on, automatic delay time before turning
the output on
Output off, automatic delay time on battery
after which output is turned off
User preferences:
Operation priority while rectifier input break
Site wiring fault w/ wrong Neutral connection [Enabled], [Disabled]
Power Strategy
Parallel settings:
Parallel unit number
Parallel operation mode
Synchronization
Start auto calibration
Parallel XCP
Minimum units to support load
Table 5 User setting in the LCD menu screen.
1026743
Revision B
[Enabled], [Disabled]
[Enabled], [Disabled]
Step: 1 Watts/cell
0 (no batteries), 1, 2, 3, 4...
Step: 0.01 V/cell
[Enabled], [Disabled]
Step: 0.1 A [max. 25 Amps]
[Disabled], [Set delay, step: 1 sec]
[Disabled], [Set delay, step: 1 sec]
[On battery], [On bypass]
[Standard], [High Efficiency]
[Single unit], [Unit #1], [Unit #2], [Unit #3],
[Unit #4]
[Redundant mode], [Capacity mode]
[Enabled], [Disabled]
[System], [Unit]
[0], [1], [2], [3], [4]
UPS 20-30 kVA, 230 V 0/60 Hz output
User's Guide
Enabled
Enabled
24 Watts/cell
1 string
1.88 V/cell
Enabled
6 Amps
0 sec.
Disabled
On battery
Enabled
Standard
Single unit
Redundant mode
Enabled
System
2