AEG Protect B. 750 PRO Operating Instructions Manual page 12

Protect b.pro series
Table of Contents

Advertisement

Rated output current (at 230 Vac)
Protect B. 750 PRO
Protect B. 1000 PRO
Protect B. 1400 PRO
Protect B. 1800 PRO
Protect B. 2300 PRO
Protect B. 3000 PRO
Power factor range
Transfer time in case of mains failure 2- 6 ms (typical), 8 ms max.
Voltage waveform
Connection
Overload capacity in mains mode
Battery
Coupled
battery
modules
with integrated
battery system
with 1 ancillary
battery unit
Temperature-dependent
charging voltage
Deep discharge protection /
Protection against overcharging
in battery mode
Autonomy times (rated load, cos
with 100% charged battery and at 25 °C
750 VA
1000 VA 1400 VA 1800 VA 2300 VA 3000 VA
3.5 min.
3.5 min.
- - -
14 min.
12
3.2 A
4.3 A
6.1 A
7.8 A
10.0 A
13.0 A
0.8 lag. to 0.9 cap.
with full power output
10% power reduction in the
range of 0.5 lag. to 0.8 lag.
Sinusoidal, distortion
< 5% THD (linear load)
< 10% THD (non-linear load)
sockets acc. to IEC 320
120% for 5 min
> 120% – 150% for 10 s
> 150% for 1 s
110% for 1 min
> 110% – 150% for 10 s
> 150% – 200% for 500 ms
> 200% for 150 ms
= 0.9 lag.)
5 min.
4.5 min.
3.5 min.
- - - 17.5 min.
Yes
Yes
4 min.
- - -
15 min.
EN