Regular Checks; Visual Check; Battery Check; Fan Check - AEG Protect B. 750 PRO Operating Instructions Manual

Protect b.pro series
Table of Contents

Advertisement

10.2 Regular checks

The following service work should be carried out:
Activity

Visual check

Battery/fan check
10.2.1 Visual check
When carrying out the visual check:
Determine whether mechanical damage or foreign bodies
can be identified in the device
Determine whether conductive dirt or dust deposits are
located in the device
Determine whether dust deposits are hindering the supply
and removal of heat.
In case of very heavy dust accumulation, the device should be
carefully blown out with dry compressed air to enable better heat
exchange.
The intervals of the visual checks to be carried out primarily
depend on the local set-up conditions of the devices.

10.2.2 Battery check

The progressive aging of the battery system can be determined
through
measurements of the achievable autonomy time every 6 months,
e.g. by simulating a mains failure. The load should always be
approximately the same as the power normally required. If the
measured autonomy time has decreased dramatically since the
previous measurement, please contact our hotline (see Page 5).

10.2.3 Fan check

The fans are to be checked regularly for dust accumulation and
any noticeable unusual noises. If the supply air openings are
Interval
6 months
6 months
CAUTION!
The Protect B. PRO must be de-energised before
the following measure is carried out.
regular
capacity
Described in
Section 10.2.1
Sect. 10.2.2/10.2.3
tests.
Carry
out
47
comparative
EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents