Omron E3NW-ECT Operation Manual page 97

Ethercat digital sensor communication unit
Hide thumbs Also See for E3NW-ECT:
Table of Contents

Advertisement

Event name
Number of Sensors Over at Distributed Sensor Unit
Meaning
Too many Sensors are connected at Distributed Sensor Unit.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
More than the maximum number of
Sensors are connected at Distributed
Sensor Unit.
Attached
None
information
Precautions/
None
Remarks
Event name
Dummy Sensors Setting Error
Meaning
Too many Dummy Units are set.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There are too many Dummy Units set,
so some Sensors are not assigned
logical unit numbers.
Attached
None
information
Precautions/
None
Remarks
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Reduce the number of Sensors at rel-
evant Distributed Sensor Unit to less
than the maximum number of Sen-
sors at Distributed Sensor Unit.
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Reduce the number of Dummy Units
that is set in the dummy function set-
tings so that logical unit numbers can
be assigned to all connected Sen-
sors, and then change the Sensors
from the Init state to Pre-operational
state or restart the Sensors.
8 Troubleshooting and Maintenance
Event code
247D0000 hex
Slave
Detection
timing
Error reset (after
Log category
automatic slave
recovery)
I/O communications and message communications are
not possible for the Sensors with relevant Distributed Sen-
sor Unit.
EtherCAT LINK/ACT
---
Name
---
Prevention
Do not connect more than the maxi-
mum number of Sensors at Distrib-
uted Sensor Unit.
Event code
34F80000 hex
Slave
Detection
timing
Errors reset
Log category
Not affected.
EtherCAT LINK/ACT
---
Name
---
Prevention
Set Dummy Units so that logical unit
numbers can be assigned to all Sen-
sor Amplifiers that are connected.
Continuously
System
When establish-
ing communica-
tions
System
8
8 - 13

Advertisement

Table of Contents
loading

Table of Contents