Inverter Applications; Operation In The Second Environment - Siemens SINAMICS G120 Hardware Installation Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical specifications
7.8 Electromagnetic compatibility of variable-speed drives
● Category C3:
Drive systems for rated voltages < 1000 V - only for operation in the second environment.
● Category C4:
Drive systems for IT line supplies for operation in complex systems in the second
environment.
An EMC plan must be created.
Note
Appropriately trained and qualified personnel
An appropriately trained and qualified person has the necessary experience for installing and/
or commissioning drive systems (Power Drive Systems - PDS), including the associated EMC
aspects.
7.8.1

Inverter applications

Inverters involve equipment used on a professional basis, deployed in certain areas of
business and industry - and are not operated in the general public domain.
For an EMC-compliant installation, observe the information provided in the Configuration
manual: EMC installation guideline
60612658).
The Power Modules described here are intended for operation in the first and second
environments. Conditions for operation in the respective environment are subsequently listed.
7.8.1.1

Operation in the second environment

Interference immunity
You do not have to take any additional measures regarding interference immunity.
Interference emission - operation in the second environment, Category C2
The drive system must comply with the following conditions in order to comply with the limit
values of the second environment, Category C2:
● The drive system is installed by appropriately qualified personnel in compliance with EMC
regulations - and the installation notes provided in the manual.
● You use a shielded motor cable with low capacitance.
● The pulse frequency is not higher than the value set in the factory.
● The drive system is connected to a TN or TT line supply.
● You comply with the permissible motor cable length.
72
Length of motor cable (Page 47).
(http://support.automation.siemens.com/WW/view/en/
Power Module PM230, IP20 / Push-through technology (PT)
Hardware Installation Manual, 08/2016, A5E34331322B AB

Advertisement

Table of Contents
loading