6 Setup
Sensitivity adjustment
(7, 8)
LED indication strip -
receive level (9)
Prerequisites
Mode
30
With these keys (7 and 8) you can adjust the switching point to the
medium.
Depending on the process, the sensitivity of VEGAMIP 61 must be set
higher or lower.
Pressing the "<--" key makes the sensor more sensitive. Pressing the
"-->" key makes the sensor less sensitive.
You can also adjust the switching delay with the two keys.
By means of the LED indicating strip, you can see the actual receive
level during adjustment.
When the indication moves to the right, the instrument is less sensi-
tive, to the left more sensitive.
6.2

Adjustment

The microwave barrier can only be adjusted when it is uncovered.
Make sure that no measured medium or vessel installations are
between the emitting and receiving unit.
Select the requested mode (min./max.) according to the function
table.
The following function table provides an overview of the switching
statuses depending on the set mode and level.
Level
Mode max.
Overflow protec-
tion
Mode max.
Overflow protec-
tion
Mode min.
Dry run protection
Mode min.
Dry run protection
Switching status Signal lamp -
Relay (yellow)
3
4
5
(6) (7)
(8)
Relay energized
3
4
5
(6) (7)
(8)
Relay deener-
gized
3
4
5
(6) (7)
(8)
Relay energized
3
4
5
(6) (7)
(8)
Relay deener-
gized
VEGAMIP R61 • Receiving unit