Mounting Instructions - Vega VEGAMIP R61 Operating Instructions Manual

Receiving unit
Table of Contents

Advertisement

4 Mounting
Switching point
Medium thickness
14
You have to remove these plugs before electrical connection.
NPT thread
In the case of instrument housings with self-sealing NPT threads, it is
not possible to have the cable entries screwed in at the factory. The
free openings for the cable glands are therefore covered with red dust
protection caps as transport protection. The dust protection caps do
not provide sufficient protection against moisture.
Prior to setup you have to replace these protective caps with ap-
proved cable glands or close the openings with suitable blind plugs.
4.2

Mounting instructions

If possible, install VEGAMIP 61 in a position where strong signal
damping by the medium is expected.
Avoid mounting the instrument too close to the vessel wall. Reflec-
tions from the vessel wall or from vessel installation can influence the
switching accuracy.
Fig. 6: Installation position (top view)
The VEGAMIP 61 requires a minimum medium thickness to detect
different products.
Dependent on the medium there will be a respective medium thick-
ness.
The properties of the medium are also dependent on the granulation
size, the bulk density and the moisture content.
Some exemplary reference values for the min. strength of the me-
dium:
Medium type
Plastic granules
Foodstuffs and wood
Medium
PTFE, PS
PP, PE, HDPE, POM
PA, PVC, PVDF
Flour
Cereals, corn, rice
Wood chips (dry)
Wood chips (moist)
VEGAMIP R61 • Receiving unit
Min. medium thickness
> 1000 mm
> 500 mm
> 250 mm
> 100 mm
> 100 mm
> 500 mm
> 100 mm