Maintenance - Samsung RC090MHXEA Installation Manual

Rc-mhxga/rc-mhxea series air to water heat pump mono outdoor unit
Hide thumbs Also See for RC090MHXEA:
Table of Contents

Advertisement

Maintenance

It is recommended that annually a competent person
a Inspects and cleans the line strainer.
b Checks the operation of the expansion relief valve and temperature & pressure relief valve.
c Recommissions the cylinder in accordance with the instructions.
Corrosion resistance
Duplex stainless steel is naturally corrosion resistant to mains water supply. No specific maintenance is required to maintain
this resistance. Please see guarantee terms for permissible water content. Please note: OSO cylinders are not guaranteed for
use with a private water supply.
The immersion heater can be removed to provide visual inspection access to the cylinder.
Tundish
Install the Tundish in a vertical position within a maximum of 600mm from the temperature and Pressure Relief Valve drain
connection. Ensure the expansion relief pipework discharges through the tundish. Tundish pipework must be 22mm with a
minimum vertical length of 300mm below tundish.
Maximum permitted length of 22mm pipework is 9m. Each bend or elbow is equivalent to 0.8m of pipework.
All pipework must have continuous fall and discharge in a safe, visible position. If any doubt, refer to Building Regulation G3.
EHS mono_RC***MHXGA_IM_E_34411A(3).indd 59
59
2012-11-26 오후 3:02:06

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents