Data Sheet; Sp-Cop1 And Sp-Cop2-Enx Modules - Wieland SP-COP1 Manual

Samos pro compact
Hide thumbs Also See for SP-COP1:
Table of Contents

Advertisement

12.3

Data sheet

888562315
12.3.1

SP-COP1 and SP-COP2-ENx modules

888563851
Table 47: SP-COP1 and SP-COP2-ENx data sheet
Safety Integrity Level
SIL claim limit
Category
Performance Level
PFHd (average probability of a ha-
zardous-causing failure per hour)
T
(usage time)
M
Protection class
Protection type
Ambient temperature during opera-
tion
Storage temperature
Humidity
Fatigue strength
Shock resistance
• Continuous shock
• Brief shock
Electromagnetic compatibility
Data interface
Configuration interface 1
Configuration interface 2
Dimensions (W × H × L)
Weight
Terminal and connection data
Single-wire or fine-strand
Fine-strand with ferrules
as per EN 46228
AWG
Maximum tightening torque
Stripping length
Wieland Electric GmbH | BA000966 | 07/2016 (Rev. C)
SP-COP1 / SP-COP-xxx
SIL3 (IEC 61508)
1
SILCL3 (EN 62061)
Category 4 (EN ISO 13849-1)
1
PL e (EN ISO 13849-1)
20 years (EN ISO 13849)
III (EN 61140)
IP 20 (EN 60529)
-25 to +65°C
-25 to +70 °C
10 to 95%, non-condensing
5 ... 150 Hz (EN 60068-2-6)
10 g, 16 ms (EN 60068-2-29)
30 g, 11 ms (EN 60068-2-27)
Class A (EN 61000-6-2, EN 55011)
Internal bus (SBUS+)
USB mini
RJ 45
45 × 96 × 115 mm
290 g (± 5%)
Screw terminal
1 x 0.2–2.5 mm
2 x 0.2–1.0 mm
1 × 0.25–2.5 mm
0.25–1.0 mm
26-14
0.5–0.6 Nm
Max. 7 mm
Technical data
Spring-loaded terminal
2
2 x 0.2–1.5 mm
2
2
or 2 ×
1 × 0.25–1.5 mm
2
zoid crimping)
24-16
2
2
(trape-
75

Hide quick links: