Wieland SP-COP1 Manual page 102

Samos pro compact
Hide thumbs Also See for SP-COP1:
Table of Contents

Advertisement

Error No.
Error type
240A0007
Warning
240A0008
Warning
240A0009
Warning
240A000A
Warning
240A000B
Warning
240Axxxx
Error
240B0001
Info
240B0002
Info
240B0003
Info
240B0004
Info
240Bxxxx
Info
240Dxxxx
Error
240Exxxx
Warning
240Fxxxx
Warning
2410xxxx
Warning
2411xxxx
Warning
2412xxxx
Warning
2413xxxx
Warning
2414xxxx
Warning
2415xxxx
Warning
2416xxxx
Warning
2417xxxx
Warning
2418xxxx
Error
2419xxxx
Warning
Wieland Electric GmbH | BA000966 | 07/2016 (Rev. C)
Logbook message
Output error on IQ4
Output error on group Q1/Q2
Output error on group Q3/Q4
Output error on group IQ1/IQ2
Output error on group IQ3/IQ4
Output error
Output error at Q1/Q2 rectified
Output error at Q3/Q4 rectified
Output error at IQ1/IQ2 rectified
Output error at IQ3/IQ4 rectified
Output error rectified
Error in system configuration
Problem with forcing
Problem with forcing
Problem with forcing
Problem with forcing
Problem with forcing
Problem with forcing
Problem with forcing
Problem with forcing
Connection problem
Forcing time expired
Internal error
Error in system configuration.
System behavior
Remedy
System continues to
Check outputs
run; affected outputs
switch off
System continues to
Check outputs
run; affected outputs
switch off
System continues to
Check outputs
run; affected outputs
switch off
System continues to
Check outputs
run; affected outputs
switch off
System continues to
Check outputs
run; affected outputs
switch off
System stop; voltage
Check outputs
OFF-ON required
System continues to
run
System continues to
run
System continues to
run
System continues to
run
System continues to
run
System stop; voltage
Reload system confi-
OFF-ON required
guration and restart
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System continues to
Restart forcing
run
System stop
Restart
System continues to
-
run
System stop; voltage
Restart or make
OFF-ON required
complaint
System continues to
Reload system confi-
run
guration
Appendix
102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents